Stainless Steel Dry-Type Sprinklers
Pendent, Horizontal Sidewall, and Extended Coverage Horizontal Sidewall
Standard and Quick Response, K-factor=5.6


Features:
  • Quick and Standard Response
  • The stainless-steel construction of these sprinklers extends the life of a sprinkler beyond that of traditional copper alloy sprinklers exposed to corrosive atmospheres
  • Wet-pipe, dry-pipe, or preaction installations
  • Designed for use in applications where sprinklers and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained
  • Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates
  • Quick and Standard Response
  • The stainless-steel construction of these sprinklers extends the life of a sprinkler beyond that of traditional copper alloy sprinklers exposed to corrosive atmospheres
  • Wet-pipe, dry-pipe, or preaction installations
  • Extended coverages protecting areas up to 16Ft. x 20Ft.(4,9 x 6,1m)
  • Designed for use in applications where sprinklers and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained
  • Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates
Hazard: All, Light Hazard/Ordinary Hazard
Temperature: 135, 155, 175, 200, 286, 360
Thread: 1"
Approval: UL, C-UL, LPCB, CE
Response: Standard Response, Quick Response
SIN Numbers: TY3250, TY3357, TY3230, TY3337, TY3339
Wrench: W7
Wrench [Recessed]: W7
Tech Data Sheet: View TFP560


Prop-65 WARNING: Cancer and Reproductive Harm -- www.P65Warnings.ca.gov
Tech Data Sheet - TFP2300 - Regulatory and Health Warnings

+ What is Proposition 65?

The purpose of Proposition 65 is to ensure the public is informed about the potential exposure to chemicals known to cause cancer, birth defects, or other reproductive harm.

The law requires the State of California to publish a list of these chemicals. This list currently contains ~1,000 chemicals; chemicals are added and removed regularly.

Johnson Controls products may have traces of various chemicals that are on the list, however they are all a part of the normal manufacturing, distribution or labeling process.


Copyright 2016 Tyco Fire Products LP. All Rights Reserved. | Careers | Privacy Policy | Cookies | Terms of Sale |