Preaction System with DV-5 Deluge Valve Double Interlock - Electric/Electric Actuation 1-1/2" thru 8" (DN40 thru DN200)


Features:
  • Double Interlock - Electric/Electric Actuation
  • The Tyco Model DV-5 Double Interlock Preaction System with Electric/ Electric Actuation is designed for use in applications, such as refrigerated areas, requiring the maximum degree of protection against inadvertent flooding of the sprinkler system piping.
  • The Model DV-5 Double Interlock Preaction System with Electric/Electric Actuation utilizes a Model DV-5 Deluge Valve and a Riser Check Valve. The Riser Check Valve isolates the Deluge Valve from the system air pressure. The releasing trim for the Deluge Valve utilizes a Solenoid Valve that is operated by energizing the releasing circuit of a Cross-Zone Deluge Valve Releasing Panel.
  • Listings and Approvals: UL, C-UL, and FM
More Information: View TFP1465
Tech Data Translations[PDF]: ES, PT

Prop-65 WARNING: Cancer and Reproductive Harm -- www.P65Warnings.ca.gov
Tech Data Sheet - TFP2300 - Regulatory and Health Warnings

+ What is Proposition 65?

The purpose of Proposition 65 is to ensure the public is informed about the potential exposure to chemicals known to cause cancer, birth defects, or other reproductive harm.

The law requires the State of California to publish a list of these chemicals. This list currently contains ~1,000 chemicals; chemicals are added and removed regularly.

Johnson Controls products may have traces of various chemicals that are on the list, however they are all a part of the normal manufacturing, distribution or labeling process.


Copyright © 2018 Johnson Controls. All Rights Reserved. | Careers | Privacy Policy | Cookies | Terms of Sale |