Page 25 - Tyco-Sprinkler-Application-Chart-Desktop
P. 25

 Notes
(1) Refer to the Technical Data Sheet for specific information. All versions of a sprinkler may not be listed or approved.
(2) Sprinkler Finish Legend (applies to cover plate only for concealed type sprinklers):
(3) Response Legend: SR = Standard Response QR = Quick Response FR = Fast Response
(4) Sprinkler Orientation: EC - Extended Coverage
ESFR - Early Supression Fast Response Opt. - Optimised
(5) Refer to the Technical Datasheet for specific information about ISO Thread availability
B =Brass
BB = Bright Brass Bl = Black
C = Chrome Plated
GW = Grey White (RAL 9002) L = Lead Coating
JB = Jet Black (RAL 9005)
SS = Stainless Steel
W = Wax Coating
Wh = Signal White (RAL 9003) WOL = Wax Coating over Lead X = Custom Color
Special(High Temperature)
 Model (1)
Issue D Quartzoid®
Issue D Quartzoid®
Issue D Quartzoid®
Issue D Quartzoid®
       Sprinkler Identification Number (SIN)
TY3191
TY3296
TY4191
TY4292
      Sprinkler Orientation
Upright
Pendent
Upright
Pendent
  Response (3)
SR
SR
SR
SR
        K Factor
  Operating Element
11 mm Bulb
11 mm Bulb
11 mm Bulb
11 mm Bulb
  Thread Size (5)
1/2"
1/2"
3/4"
3/4"
       Data Sheet
TFP690
TFP690
TFP690
TFP690
        Base Part No.
51-036
51-040
51-136
51-140
           Temperature °F (1)
400, 500, 650
400, 500, 650
400, 500
400, 500
   Max. Pressure
   Sprinkler Finish (1,2)
B, C, L
B, C, L
B, C, L
B, C, L
      Approvals (1)
FM, UL, C-UL, LPCB
FM, UL, C-UL, LPCB
UL, C-UL
UL, C-UL
   Wrench
W11
W11
W11
W11
            Recessed Wrench
      Recessed Escutcheon (1)
   LPM/ bar1/2
80.6
80.6
115.2
115.2
          GPM/ psi1/2
5.6
5.6
8.0
8.0
       bar
12.1
12.1
12.1
12.1
          PSI
175
175
175
175
            www.tyco-fire.com