Page 24 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 24

 Fire Suppression General Products Catalog
 Storage Sprinklers
LD "Large Drop"
Upright, Control Mode Specific Application
     K Factor
K=11.2 (161,3)
  Thread Size
3⁄4" NPT
         5 mm bulb • Control mode sprinkler • Can provide a higher level of protection than standard spray sprinklers • Can provide an advantage by eliminating in-rack sprinklers • Designed for the protection of high-piled storage
    TY-B
Pendent & Upright, Intermediate Level
Approvals
Temperature
UL, C-UL, NYC
155°F/68°C, 200°F/93°C, 286°F/141°C
   Sprinkler Finish
Natural Brass
   SIN
TY5153
   Wrench Type
W-TYPE 3
  Tech Data Sheet
TFP335
      K Factor
K=5.6 (80,6) • K=8.0 (115,2)
  Thread Size
 Temperature
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
24
1⁄2" NPT • 3⁄4" NPT
  Approvals
UL, C-UL, FM, NYC
  135°F/57°C, 155°F/68°C, 175°F/79°C, 200°F/93°C, 286°F/141°C, 360°F/182°C
   Sprinkler Finish
Natural Brass, Lead Coated, Wax Coated, Wax over Lead Coated
   SIN
TY3153, TY3251, TY4153, TY4251
   Wrench Type
W-TYPE 6
  Tech Data Sheet
TFP351
   5 mm bulb • Intermediate level (in-rack) with shield • Used where sprinkler guards are not required • Factory assembled unit having an integral water shield • Both the Pendent and Upright Sprinklers produce a hemispherical water distribution pattern below the deflector.
    