Page 21 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 21

 www.tyco-fire.com
 ULTRA K-17
Upright, Control Mode Specific Application
Upright, Control Mode Specific Application, 286° F
Storage Sprinklers
     K Factor
   Approvals
UL, C-UL, FM, NYC
   Temperature
155°F/68°C, 200°F/93°C
   Sprinkler Finish
Natural Brass
   SIN
TY7153
   Wrench Type
W-TYPE 8
  Tech Data Sheet
TFP330
   5 mm bulb • Approved for storage heights of 25' (7,6 m) and building heights to 30' (9,1 m) • Full-scale fire testing has shown that the Ultra K17 can control fires with commodities up to Group A plastics, and eliminate the need for in-rack sprinklers.
      K Factor
K=16.8 (241,9)
   Thread Size
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
K=16.8 (241,9)
  Thread Size
3⁄4" NPT
 3⁄4" NPT
  Temperature
286°F/141°C
   Sprinkler Finish
Natural Brass
   Wrench Type
W-TYPE 8
  Tech Data Sheet
Contact Tyco for Details
   5 mm bulb • Control mode sprinkler