Page 20 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 20

 Fire Suppression General Products Catalog
 Storage Sprinklers
ESFR-17
Dry-Type Pendent
        Early Suppression, Fast Response (ESFR) • Solder type • Eliminates in-rack sprinklers for box-in-box applications • Suppression
mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled box-in-
box refrigerated storage areas • The drop between the inlet and sprinkler remains dry until the sprinkler operates, allowing for a pendent sprinkler installation on a wet pipe sprinkler system where the dry drop and sprinkler are located in an area subjected to freezing temperatures • Less costly to install and maintain than pre-action or antifreeze systems • The Model ESFR-17 Dry Type Pendent Sprinkler is FM Approved and has successfully undergone full-scale fire testing at FM Global, when used in conformance with applicable FM Global Property Loss Prevention Data Sheets • The Model ESFR-17 Dry Type Sprinklers are primarily used for ceiling only sprinkler protection and used to protect solid piled, palletized, and rack storage that is subject to freezing temperatures
ESFR-14
Pendent
K Factor
Approvals
K=16.8 (241,9)
   Thread Size
1-1⁄4" NPT or ISO 7-R 1-1⁄4
   Grooved End
2" Standard Cut Grooved per Tech Data Sheet TFP1898
 UL, FM
   Temperature
165°F/74°C, 212°F/100°C
   Sprinkler Finish
Natural Brass
   SIN
TY7229
   Wrench Type
W-TYPE 26
  Tech Data Sheet
TFP320
               K Factor
K=14.0 (201,6)
   Thread Size
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
20
3⁄4" NPT or ISO 7-1
   Approvals
UL, C-UL, FM
   Temperature
155°F/68°C, 200°F/93°C
   Sprinkler Finish
Natural Brass
   SIN
TY6236
   Wrench Type
W-TYPE 34
  Tech Data Sheet
TFP319
   Early Suppression, Fast Response (ESFR) • 3mm bulb type • Designed for the protection of rack storage • Direct attack on burning fuel by improved heavy sprinkler discharge • They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.
    




















































   18   19   20   21   22