 Fire Suppression General Products Catalog
 Special Application Sprinklers
TY-B & TY-FRB (Poly-Stainless)
Upright, Pendent & Horizontal Sidewall Sprinklers
     K Factor
K=5.6 (80,6) • K=8.0 (115,2)
   Thread Size
 Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
54
1⁄2" NPT • 3⁄4" NPT
   Approvals
UL, C-UL, LPCB, Lloyds
   Temperature
57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F, 141°C/286°F, 182°C/360°F
  Escutcheon Style
Style 10 • Style 40
   Sprinkler Finish
Poly-Stainless
   SIN
Refer to Tech Data Sheet for SIN Numbers
   Wrench Type
TY-B: 5 mm diameter heat sensitive glass bulb, standard response • TY-FRB: 3 mm diameter heat sensitive glass bulb, quick response • Corrosion resistant, standard coverage spray sprinklers designed for use in commercial occupancies where corrosive atmospheres may exist • Corrosive environments can wreak havoc on standard sprinkler heads. The TYCO Poly-Stainless sprinklers are here to maintain the aesthetics of a sprinkler in a wide range of corrosive locations.
W-TYPE 6, W-Type 7 (For recessed escutcheons)
  Tech Data Sheet
TFP682
      