Page 50 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 50

 Fire Suppression General Products Catalog
 Special Application Sprinklers
Issue D Quartzoid®
High Temperature, Upright & Pendent
     K Factor
K=5.6 (80,6), K=8.0 (115,2)
  Thread Size
1⁄2" NPT • 3⁄4" NPT
       Standard coverage • All hazard • 11 mm bulb • Extra-high and ultra-high temperature ratings and corrosion resistant coatings • Temperature Ratings to 343°C (650°F) available.
    TY-B
Conventional (Old Style)
Approvals
Temperature
UL, C-UL, FM, LPCB
204°C/400°F, 260°C/500°F, 343°C/650°F (K=5.6 only)
   Sprinkler Finish
Natural Brass, Chrome Plated, Lead Coated
   SIN
TY3191, TY3296, TY4191 , TY4292
   Wrench Type
W-Type 11
  Tech Data Sheet
TFP690
      K Factor
K=5.6 (80,6) , K=8.0 (115,2)
  Thread Size
 Temperature
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
50
1⁄2" NPT • 3⁄4" NPT
  Approvals
UL, C-UL, LPCB, VdS, NYC
  57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F, 141°C/286°F, 182°C/360°F, Open
   Sprinkler Finish
Natural Brass, Chrome Plated, Pure White, Signal White, Wax Coated, Lead Coated, Wax Over Lead Coated
   SIN
TY3651, TY4651
   Wrench Type
Ordinary and Extra High Hazard • 5 mm bulb • These sprinklers are intended to be installed either pendent or upright, and in either position, they produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and approximately 50% of the discharge directed downwards. • The NFPA permits the use of “Old Style Sprinklers” where special construction features require a unique water distribution.
W-Type 6
  Tech Data Sheet
TFP661
      