Page 49 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 49

 www.tyco-fire.com
 CC2
Combustible Concealed Space SprinklersTM, Upright
Special Application Sprinklers
     K Factor
K=4.2 (60,5), K=5.6 (80,6)
             CC3
Combustible Concealed Space SprinklersTM, Upright
Thread Size
Temperature
1⁄2" NPT
   Approvals
UL
79°C/175°F
   Sprinkler Finish
Natural Brass
   SIN
TY2189, TY3189
   Wrench Type
W-Type 6
  Tech Data Sheet
TFP632
   3 mm bulb • Specific application sprinklers • Provides protection of specific light hazard combustible, as well as non-combustible, concealed spaces requiring sprinkler protection • The CC2 Sprinklers comply with the criterion for the protection of combustible concealed spaces as described in NFPA 13 • Allows the use of BlazeMaster® CPVC pipe in combustible concealed areas with the benefit of superior sprinkler protection for Wood truss spaces • Can be used on steel dry pipe sprinkler systems • Increased spacing from 3,1 m (10 ft.) to 3,7 m (12 ft.) • Increased coverage area from 9,3 m2 (100 ft2) to 13,4 m2 (144 ft2)
     K Factor
K=4.2 (60,5), K=5.6 (80,6)
   Thread Size
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
1⁄2" NPT
   Approvals
UL
   Temperature
93°C/200°F
   Sprinkler Finish
Natural Brass
   SIN
TY2199 - 4.2K, TY3199 - 5.6K
   Wrench Type
W-Type 6
  Tech Data Sheet
TFP633
   3 mm bulb • The CC3 Combustible Concealed Sprinklers are quick response, upright, specific application sprinklers designed to provide protection of specific light hazard combustible, as well as non-combustible, concealed spaces requiring protection • The Model CC3 Sprinklers comply with the criteria for the protection of combustible concealed spaces as described in NFPA 13 • The Model CC3 are designed for installation on BlazeMaster CPVC wet pipe systems and steel wet pipe or dry pipe sprinkler systems.
     Combustible Concealed Sprinkler Discharge Pattern
Standard Spray Sprinkler Discharge Pattern
www.tyco-fire.com 49