Page 31 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 31

 www.tyco-fire.com
 LFII
Pendent & Recessed Pendent
Rapid Response® Sprinklers
     K Factor
K=3.0 (43,2)
  Thread Size
1⁄2" NPT
        Horizontal & Recessed Horizontal Sidewall
Approvals
Temperature
UL, C-UL, NSF/ANSI 61
68°C/155°F, 79°C/175°F
  Escutcheon
Style 20
   Sprinkler Finish
Signal White, Chrome Plated, Natural Brass
   SIN
TY1234
   Wrench Type
W-TYPE 6, W-Type 7 (For recessed escutcheons)
 Tech Data Sheet
TFP402
   3 mm bulb type • Decorative, fast response, frangible bulb sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels.
Intended for use in these wet pipe scenarios:
- residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D - residential occupancies up to and including four stories in height per NFPA 13R
- sprinkler systems for the residential portions of any occupancy per NFPA 13
     K Factor
K=4.4 (63,4)
  Thread Size
1⁄2" NPT
    Approvals
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
UL, C-UL, NSF/ANSI 61
   Temperature
68°C/155°F, 79°C/175°F
  Escutcheon
Style 20
   Sprinkler Finish
Signal White, Chrome Plated, Natural Brass
   SIN
TY2334
   Wrench Type
W-TYPE 6, W-Type 7 (For recessed escutcheons)
  Tech Data Sheet
TFP412
   3 mm bulb type
Intended for use in these wet pipe scenarios:
- residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D - residential occupancies up to and including four stories in height per NFPA 13R
- sprinkler systems for the residential portions of any occupancy per NFPA 13
www.tyco-fire.com 31