 Storage Sprinklers
TY-FRB
Pendent & Upright, Intermediate Level
     K Factor
K=5.6 (80,6)
   Thread Size
1⁄2" NPT
  Approvals
UL, C-UL, FM
  Temperature
57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F, 141°C/286°F
     TY-L
Pendent & Upright, Intermediate Level
Sprinkler Finish
Natural Brass
   Guard Finish
Red or Zinc
   SIN
TY313, TY323
   Wrench Type
Tech Data Sheet
W-TYPE 6
 TFP357
   3 mm bulb • Factory assembled unit having an integral water shield • Intermediate Level Sprinklers are primarily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher elevation sprinklers that could operate earlier during a fire • May also used in other applications such as beneath open gridded catwalks
        K Factor
K=5.6 (80,6) • K=8.0 (115,2)
   Thread Size
Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
26
1⁄2" NPT • 3⁄4" NPT
   Approvals
UL, C-UL, FM
   Temperature
74°C/165°F, 100°C/212°F, 138°C/ 280°F
   Sprinkler Finish
Natural Brass
   SIN
TY3113, TY3211, TY4113, TY4211
   Wrench Type
Solder type • Intermediate level with shield • Factory assembled unit having an integral water shield • Used where sprinkler guards are not required
W-TYPE 9
  Tech Data Sheet
TFP350
      






















































   24   25   26   27   28