Page 22 - Fire Suppression General Products Catalog, Automatic Sprinklers, System Valves and Devices, Piping and Electrical Products
P. 22

 Fire Suppression General Products Catalog
 Storage Sprinklers
ESFR-14
Pendent
     K Factor
K=14.0 (201,6)
     K17-231
Pendent & Upright
Thread Size
Sprinkler Finish
3⁄4" NPT or ISO 7-1
   Approvals
UL, C-UL, FM
   Temperature
68°C/155°F, 93°C/200°F
 Natural Brass
   SIN
TY6236
   Wrench Type
W-TYPE 34
  Tech Data Sheet
TFP319
   Early Suppression, Fast Response (ESFR) • 3mm bulb type • Designed for the protection of rack storage • Direct attack on burning fuel by improved heavy sprinkler discharge • They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.
         K Factor
K=16.8 (241,9)
   Thread Size
3⁄4" NPT
   Approvals
 ELO-231B
Pendent & Upright
     Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
22
Upright= UL, C-UL, FM, NYC Pendent= UL, C-UL, NYC
   Temperature
68°C/155°F, 93°C/200°F, 141°C/286°F
   Sprinkler Finish
Natural Brass
   SIN
TY7151, TY7251
   Wrench Type
W-TYPE 8
  Tech Data Sheet
TFP332
   5 mm bulb • They are “standard response spray sprinklers” which produce a hemispherical water distribution pattern below the deflector • Low-pressure requirement (as low as 0.48 bar (7 psi)) can save cost by reducing branch line size, taking advantage of maximized spacing, and upgrading existing densities • Very large orifice sprinkler for use in high challenge storage occupancies.
     K Factor
K=11.2 (161,3)
  Thread Size
1⁄2" NPT • 3⁄4" NPT
   Approvals
UL, C-UL, FM, NYC
   Temperature
68°C/155°F, 93°C/200°F, 141°C/286°F
   Sprinkler Finish
Brass, Chrome Plated, Lead Coated, Wax Coated, Wax over Lead Coated
   SIN
TY5151, TY5251, TY5851
   Wrench Type
W-TYPE 3
  Tech Data Sheet
TFP342
   5mm bulb • Extra large orifice sprinklers proven for storage through full-scale fire testing • Can be used as intermediate level version by adding a guard and shield • Designed to control high challenge fires with relatively low required pressures
   