Page 26 - Red-E Cabinet DV-5A Installer's Manual
P. 26

   (FIELD WIRED)
OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS
5.1K
3.2
5.1K
8.1
+ -
ZONE 3 VALVE TAMPER
8.2
8.2
+ -
ZONE 4 WATERFLOW SWTCH
TERMINAL BLOCK LOCATED INSIDE THE POTTER PFC-4410-RC CONTROL PANEL
5.2
5.1
1.1
1.2
5.1K
                                                   2.1
2.2
5.1K
                 TO CIRCUIT BREAKER PANEL
3.1
5.1K
          120VAC / 6OHz 165 VA MAX. 220VAC / 50Hz 185 VA MAX.
120 VOLT MODEL 220 VOLT MODEL
                2.1
2.2
  EARTH GROUND - GREEN NEUTRAL - WHITE HOT - BLACK
EG N 120 AC IN CONNECTOR
NON-POWER LIMITED AND SUPERVISED
+ - + - S
+ -
AUX. POWER
5.1K
+ - SUP 1/
ABORT
+ - SUPV 2
+ -
ZONE 1 HEAT OR SMOKE DETECTORS
+ -
ZONE 2 LOW AIR ALARM
                                                          24 VDC
RS-485
   PANEL INPUTS (INITIATING ZONES) CONNECT TO NORMALLY OPEN DEVICES OR COMPATIBLE 2 WIRE SMOKE DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS (EXCEPT WITH LINEAR HEAT DETECTION)
   RED OUTPUT LED STEADY: ABORT
 ZONE 1
     ZONE 2
         ZONE 3
          ZONE 4
       OUTPUT 1
    OUTPUT 2
      OUTPUT 3
     OUTPUT 4
   RUN PROGRAM
SUP 1/ ABORT
SUPERVISORY 2
COMMON ALARM
ALARM SILENCE
STEADY DISCHARGED SET
AC POWER POWER TBL SYSTEM TBL SUP TBL GROUND FAULT
VIEWING ANGLE
PROGRAM MODE
RUN MODE
SCROLL UP BUZZER SILENCE
LAMP TEST
SCROLL DOWN BUZZER SILENCE
SIGNAL SILENCE SYSTEM RESET
           FLASHING: PRE- DISCHARGED
  SELECT FUNCTION
   OPTIONAL CA2Z MOUNTING LOCATION
 PANEL OUTPUTS (INDICATING CIRCUITS)
 GENERAL WATER
ALARM BELL
NON-POWER LIMITED AND SUPERVISED
BATT
+- -+-+-+-+
RELEASE WATER
FLOW
BELL CIRCUIT
FLOW OUTPUT 4
RELAY CONTACTS
DRY CONTACTS RATED AT 3A, 30VDC
   OUTPUT 1
OUTPUT OUTPUT 2 3
ALARM COMNO NC
ALARM CONDITION SMOKE DET. HEAT DET. PULL STATION WATERFLOW
SUPV
COMNO COMNO
SUPERVISORY LOW AIR VALVE TAMPER
   5.1K
TROUBLE COMNO NC
TROUBLE CONDITION PANEL PROBLEM LOSS OF AC LOSS OF BATTERY WIRING PROBLEM
WTRFL
                                         BATTERY CABLE OBSERVE POLARITY RED + BLACK -
12V BATT.
5.1K
(FIELD WIRED)
4.1
5.1K
(FIELD WIRED)
RED
WATERFLOW
                                   +- POS NEG
  P
   +- OS NEG
          5.1K
EOL DIODE ASSEMBLY
ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE PFC-4410RC INSTALLATION, OPERATION AND INSTRUCTION MANUAL
USED WITH STANDARD PROGRAM #13
4.2 SOLENOID
(FIELD WIRED)
8.1
   12V BATT.
NOTES:
   Red-E DV-5A Double-Interlock Pre-Action (Electric-Electric) Wiring Schematic
21
(FIELD WIRED)
(FIELD WIRED)
(NOT USED)
PS-10 WATERFLOW
PS-10 LOW AIR SWITCH SUPERVISORY
PS-10 LOW AIR ALARM SWITCH
STANDARD WIRING
SYSTEM MAIN VALVE
SYSTEM SHUT-OFF VALVE
STANDARD WIRING
BLACK RED
BLACK BLACK
BLACK
   24   25   26   27   28