Page 20 - Red-E Cabinet DV-5A Installer's Manual
P. 20

Double Interlock Preaction (Electric-Electric)
The PFC-4410RC has more than 20 standard programs which are detailed in the Installation, Operation and Instruction Manual for the Potter PFC-4410RC. Red-E Cabinet Double Interlock Preaction (Electric-Electric) configurations are pre-wired to function with standard program #13.
CAUTION
Selecting a standard program other than #13 can cause unintended results if pre-wired devices are re-assigned (e.g. supervisory switch assigned as a manual dump).
If the standard program is not acceptable for the installation required, select the custom program #0 then press the SET button. This will allow the user to custom program the panel. Refer to PFC- 4410RC Custom Program Information for Water Based Extinguishing Systems in Installation, Operation and Instruction Manual for the Potter PFC-4410RC for custom program information.
PROGRAM #13 MODE
1. Apply power to panel.
2. Move the program switch to PROGRAM.
3. Press the FUNCTION button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the symbol, then press the SET button to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)
5. Press the FUNCTION button until the display reads “PROGRAM #”.
6. Press the SELECT button until the display reads “PROGRAM #13”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages.
The panel should now display: