   Red-E DV-5A Deluge, Single Interlock Preaction, Double Interlock Preaction (Pneumatic-Electric) Program
             ZONES
    SUP 1
       SUP 2
    #1
   #2
      #3
       #4
   OUTPUTS
     Supervisory
    Low Air Supervisory
  Conventional
 Conventional
   Tamper
     Waterflow
   GENERAL ALARM
           X
  X
        X
  WATERFLOW BELL
        X
  SOLENOID VALVE (#7)
                 X
    X
               WATERFLOW ALARM
                     X
  Description: Red-E DV-5A Deluge, Single Interlock Preaction or Double Interlock Preaction (Pneumatic-Electric) release for single hazard
Inputs: 2 supervisory zones*, 2 conventional detection zones, 1 valve tamper zone, 1 waterflow alarm zone
Outputs: 1 general alarm, 2 waterflow, 1 solenoid release circuit
Operation:
Activation of either conventional detection zone will operate the release and the general alarm output, and cause the alarm contact to change state.
Activation of the wateflow zone will operate the general alarm bell output, the waterflow output, the alarm contact, and cause the waterflow contact to change state.
Activation of any of the tamper or supervisory zones will operate the supervisory relay only. When either zone 1 or 2 is in alarm, outputs 1 & 3 will operate
When zone 1 and 2 is in alarm, outputs 1 & 3 will operate
When zone 3 or either supervisory zones is activated, only the supervisory relay operates When zone 4 is in alarm, outputs 1, 2, & 4 will operate
* The low air supervisory zone is not used on Deluge electric release and wet pilot release models